MACH-ProZone
BACnet® Controller
Small, durable and packed with flexibility, the Reliable Controls MACH-ProZone is a fully programmable BACnet Building Controller (B-BC) with highly scalable I/O in a very small footprint. The MACH-ProZone is ideal for a wide range of applications that include small to mid-sized roof top and heatpump applications, and small mechanical room applications.
Features
Dynamic Database
- Allows a maximum of 128 objects to be created of any supported type in any model of controller
- Typical Object Configuration table (below) shows the usage of expanded memory
Protocol
- BACnet® - MS/TP (EIA-485)
Control-BASIC™ Programs
- 8500 bytes of programmable control strategy in a readable, BASIC-like language
- 3200 bytes per program
Inputs
- Universal ranges
- Soft-selectable 0-10 VDC,
4-20 mA, thermistor / dry contact
Outputs
- Universal ranges
- Jumper selectable 0-12 VDC,
or TRIAC
Variables
- Selectable standard and custom ranges, as well as fixed or program-driven values
PID Loops
- Standard P, PI, or PID controllers for closed loop control
Single-Point Trend Logs
- Stores 128 samples at programmable time intervals
Multipoint Trend Logs
- Each Trend Log stores 128 samples of 8 points at programmable time intervals
Runtime Report
- Records the total On time and the total number of transitions, as well as daily transitions for every binary point
- A 50 sample runtime log is optional for each binary point
System Groups
- Allows related points to be grouped onto one display
- 80 points/group
Schedules
- 7 On/Off times for each weekday or exception
Calendars
- Days of the year designated as holidays
Arrays
- Up to 128 elements in a one-dimensional array
Tables
- For creating custom input ranges and Control-BASIC™ lookup tables
Custom Units
- 8 analog engineering units
- 8 binary engineering units
- 8 multistate units with 8 states, 32-characters each
SMART-Net Port
- Networks up to 8
SMART-Sensors™
64 Network In Points
32 Network Out Points
- The total maximum number of writes and shares to other devices
Warranty
- 5 years
Certification
- BTL Listed (B-BC)
- CE
- CFR47 Part 15/B
- UL916 Listed
Typical Object Configuration
There are physical limitations to the number of inputs, outputs, and SMART-Sensors that can be connected to a MACH-ProZone controller. For other object types, there are no imposed limits for the maximum number of objects of a single type that can be created. The total number of objects (including inputs, outputs, and SMART-Sensors) is limited to 128, and is also limited by the onboard memory. The table below details typical databases that fit in all models
Memory (-MX & MPZ-88) Variables (64) Loops (8) Schedules (4) Calendars (2) Tables* (4) Groups (4) Multipoint Trend** (10) Runtime* (128) Arrays (4) Program (8) SMART-Sensor*** (8)
* Tables and Runtime Logs are not counted in the 128 object limit. Inputs, outputs, and the device object are counted in the 128 object limit.
** Trends are configured to store 128 samples.
*** All models accommodate a maximum of 8 SMART-Sensors.
Tech Specs
Processor
- 66 MHz, high performance, 32-bit embedded microcontroller with onboard Flash memory
- Controller database, values and configuration held in robust non-volatile memory
- Operating System firmware easily updated at any time over the network
Supply Voltages
- 24 VAC ±10% 25 VA max. 50/60 Hz
- 24 VDC ±10% 12 W max.
Communications
- EIA-485 @ 76.8 kbps max.
- SMART-Net™ (8 SMART-Sensors™ max.)
- Auto-baud detection
Universal Inputs
- 12-bit A/D converter
- Soft selectable: 0-10 VDC, 4-20 mA, thermistor/dry contact
- Impedance:
3M Ω on 0-10 VDC range
250 Ω on 4-20 mA range
20k Ω on thermistor range - Pulse counting up to 40 Hz
(supports flow meters) - 24 VAC over-voltage protection
Universal Outputs
- 12-bit D/A converter
- Analog: 0-12 VDC
- Binary: 0/12 VDC
- Output power: 75 mA @ 12 VDC
- 24 VAC over-voltage and short protection
- Jumper selectable TRIAC
TRIAC Outputs
- 24 VAC @ 0.5 A
SETUP-Tool™
- SETUP-Tool™ optional for configuration
Real-time Clock (optional)
- ±5 seconds per month
Memory/RTC Backup (-C models)
- Clock operation is maintained for over one year with no external power
- Ten years for database
Terminal Blocks
- 12 to 30 AWG (3.31 mm² to 0.05 mm²)
- Stranded or solid core
- Copper conductors only
Dimensions
- 10.9 cm L x 19.1 cm W x 4.6 cm H
(4 5/16" L x 7 1/2" W x 1 13/16" H)
Mounting
- DIN rail, or
- #8 clearance holes on 17.8 cm W (7" W) centerline
Weight
- 0.3 kg (0.7 lb.)
Ambient Limits
- Operating: -20 ºC to 55 ºC
(-4 ºF to 131 ºF) - Shipping: -40 ºC to 60 ºC
(-40 ºF to 140 ºF) - Humidity: 10% to 90%
RH non-condensing