2 Victoria St. Milton, ON

MACH-ProZone


MACH-ProZone

 
 

BACnet® Controller
Small, durable and packed with flexibility, the Reliable Controls MACH-ProZone is a fully programmable BACnet Building Controller (B-BC) with highly scalable I/O in a very small footprint. The MACH-ProZone is ideal for a wide range of applications that include small to mid-sized roof top and heatpump applications, and small mechanical room applications.

 
 
 

Features

 

Dynamic Database

  • Allows a maximum of 128 objects to be created of any supported type in any model of controller
  • Typical Object Configuration table (below) shows the usage of expanded memory


Protocol

  • BACnet® - MS/TP (EIA-485)


Control-BASIC™ Programs

  • 8500 bytes of programmable control strategy in a readable, BASIC-like language
  • 3200 bytes per program


Inputs

  • Universal ranges
  • Soft-selectable 0-10 VDC, 
    4-20 mA, thermistor / dry contact


Outputs

  • Universal ranges
  • Jumper selectable 0-12 VDC, 
    or TRIAC


Variables

  • Selectable standard and custom ranges, as well as fixed or program-driven values

 

    PID Loops

    • Standard P, PI, or PID controllers for closed loop control


    Single-Point Trend Logs

    • Stores 128 samples at programmable time intervals


    Multipoint Trend Logs

    • Each Trend Log stores 128 samples of 8 points at programmable time intervals


    Runtime Report

    • Records the total On time and the total number of transitions, as well as daily transitions for every binary point
    • A 50 sample runtime log is optional for each binary point


    System Groups

    • Allows related points to be grouped onto one display
    • 80 points/group


    Schedules

    • 7 On/Off times for each weekday or exception


    Calendars

    • Days of the year designated as holidays

     

      Arrays

      • Up to 128 elements in a one-dimensional array


      Tables

      • For creating custom input ranges and Control-BASIC™ lookup tables


      Custom Units

      • 8 analog engineering units
      • 8 binary engineering units
      • 8 multistate units with 8 states, 32-characters each


      SMART-Net Port

      • Networks up to 8
        SMART-Sensors™


      64 Network In Points


      32 Network Out Points

      • The total maximum number of writes and shares to other devices


      Warranty

      • 5 years


      Certification

      Typical Object Configuration

      There are physical limitations to the number of inputs, outputs, and SMART-Sensors that can be connected to a MACH-ProZone controller. For other object types, there are no imposed limits for the maximum number of objects of a single type that can be created. The total number of objects (including inputs, outputs, and SMART-Sensors) is limited to 128, and is also limited by the onboard memory. The table below details typical databases that fit in all models

      Memory (-MX & MPZ-88)     Variables (64)     Loops (8)     Schedules (4)     Calendars (2)     Tables* (4)     Groups (4)     Multipoint Trend** (10)     Runtime* (128)     Arrays (4)     Program (8)      SMART-Sensor*** (8)

      * Tables and Runtime Logs are not counted in the 128 object limit. Inputs, outputs, and the device object are counted in the 128 object limit. 
      ** Trends are configured to store 128 samples.
      *** All models accommodate a maximum of 8 SMART-Sensors.



      Tech Specs

      Processor

      • 66 MHz, high performance, 32-bit embedded microcontroller with onboard Flash memory
      • Controller database, values and configuration held in robust non-volatile memory
      • Operating System firmware easily updated at any time over the network


      Supply Voltages

      • 24 VAC ±10% 25 VA max. 50/60 Hz
      • 24 VDC ±10% 12 W max.


      Communications

      • EIA-485 @ 76.8 kbps max.
      • SMART-Net™ (8 SMART-Sensors™ max.)
      • Auto-baud detection


      Universal Inputs

      • 12-bit A/D converter
      • Soft selectable: 0-10 VDC, 4-20 mA, thermistor/dry contact
      • Impedance:
        3M Ω on 0-10 VDC range
        250 Ω on 4-20 mA range
        20k Ω on thermistor range
      • Pulse counting up to 40 Hz
        (supports flow meters)
      • 24 VAC over-voltage protection


      Universal Outputs

      • 12-bit D/A converter
      • Analog: 0-12 VDC
      • Binary: 0/12 VDC
      • Output power: 75 mA @ 12 VDC
      • 24 VAC over-voltage and short protection
      • Jumper selectable TRIAC


      TRIAC Outputs

      • 24 VAC @ 0.5 A

      SETUP-Tool™

      • SETUP-Tool™ optional for configuration


      Real-time Clock (optional)

      • ±5 seconds per month


      Memory/RTC Backup (-C models)

      • Clock operation is maintained for over one year with no external power
      • Ten years for database


      Terminal Blocks

      • 12 to 30 AWG (3.31 mm² to 0.05 mm²)
      • Stranded or solid core
      • Copper conductors only


      Dimensions

      • 10.9 cm L x 19.1 cm W x 4.6 cm H
        (4 5/16" L x 7 1/2" W x 1 13/16" H)
         

      Mounting

      • DIN rail, or
      • #8 clearance holes on 17.8 cm W (7" W) centerline


      Weight

      • 0.3 kg (0.7 lb.)


      Ambient Limits

      • Operating: -20 ºC to 55 ºC
        (-4 ºF to 131 ºF)
      • Shipping: -40 ºC to 60 ºC
        (-40 ºF to 140 ºF)
      • Humidity: 10% to 90%
        RH non-condensing